Specification:
Primary windings
- terminals inputs 1 & 2: voltage 115 Vac 60Hz
open circuit 160 mA max
full load current 3.6 Amps
- terminals inputs 1 & 3: voltage 230Vac 50Hz
open circuit current 80 mA max
full load current 1.8 Amps
Secondary windings
- terminals output 4 & 5: open circuit voltage 80,0 Vac
full load voltage 85 Vac (±3%)
full load current 4.37 Amps
- terminals output 6 & 7: open circuit voltage 18 Vac
full load voltage 19,2 Vac (±3%)
full load current 2.77 Amps
Rated output power
400 Watts
Insulation resistance
- 100 Mohm @ 500 Vdc between primary and secondary
- 100 Mohm @ 500 Vdc between secondary 1 and secondary 2 and secondary 3
- 100 Mohm @ 500 Vdc between secondary 2 and secondary 3
Insulation class
Class B
Dielectric strength
- 4300 Vac, 5 mA, 1 minute between primary and secondary
- 3000 Vac, 5 mA, 1 minute between secondary 1 and secondary 2 and secondary 3
- 500 Vac, 5mA, 1 minute between secondary 2 and secondary 3
Protection device
on primary winding termic at 110°C (250V 5.0A)
Ambient temperature
-20°C ~ +80°C
Max winding temperature
55°C